DIFFERENTIAL PRESSURE FLOW METERS

Differential Pressure Flow Meters

Differential pressure flow meters use a primary element inside a pipe to create a constriction and pressure drop for flow measurement.

When the primary element is used in conjunction with a differential pressure transmitter, the volumetric flow rate may be calculated as a function of the differential pressure across the obstruction; hence the term “differential pressure flow meter”. 

DP flow measurement in one of the oldest flow measurement technologies and dates back to at least the 17th century — though the measurement of flow using nozzles actually goes all the way back to Roman times. In 1738, Daniel Bernoulli developed his famous equation for flow rate calculation which shows that increasing velocity by constricting a flow path increases fluid pressure. Restricting the flow path creates an increased pressure and if you can measure the upstream and downstream pressure, you can calculate the flow rate.

ACONE

  • Acone flow element used with either ALDPT or ALDPTMV

  • ½~10" (15-250 mm)

  • Based on Re > 8000 For gases, liquids and steam

  • 320~1500°F (-196~850 °C)

  • Liquid: ± 0.5% of reading Gas & Steam: ± 1.0% of reading

  • SS #304L/SS #316L, CPVC ,PTFE, Brass, A106B A335-P11, A335-P22, Dual - Phase Steel, Inconel 625, Hastelloy C276

  • 4~20 mA square root output, HART, MODBUS

  • NPT, flanged (JIS, ANSI and DIN), wafer or butt weld

  • Where space is limited; reduced straight pipe requirements of 0-3 D upstream and 0-1 D downstream

  • Any application where the flow engineer prefer DP flow meters; extreme high temp applications

ALDPT with ACONE

  • Differential Pressure

  • Any

  • Available for DP of up to 0 -2Mpa (290 PSI)

  • –4-752°F(-20- 400)°C

  • ±0.5%, ±0.2%, ±0.075% of reading

  • SS #316L, Hastelloy C, Tantalum, Gold Plated

  • 4~20 mA square root output, HART, MODBUS

  • ¼“-18 NPTF & ⁷⁄₁₆"-20 UNF, no drain or with drain top, side or bottom of flange

  • 3 or 5-way valve manifold for primary DP flow element (ACONE), 2" pipe mounting brackets, O2 cleaning, capillaries (many fill fluids)

  • Stand alone DP measurement or with primary flow elements: Orifice, Venturi, ACONE, Pitot Tube, Wedge, Elbow

ALDPT-MV with ACONE

  • Multi-variable Differential Pressure

  • Any

  • Based on DP of 0 -2Mpa (290 PSI)

  • –4-752°F(-20- 400)°C

  • ±0.2%, ±0.075% of reading

  • SS #316L, Hastelloy C, Tantalum

  • 4~20 mA square root output, HART, MODBUS

  • ¼“-18 NPTF & ⁷⁄₁₆"-20 UNF, no drain or with drain top, side or bottom of flange

  • 3 or 5-way valve manifold for primary DP flow element (ACONE), 2" pipe mounting brackets, O2 cleaning, capillaries (many fill fluids)

  • Where multiple parameter measurement such as flow, DP, temperature, mass flow is required from one instrument